Free UK Rafter Calculator for roof construction. Calculate rafter length, angle, birdsmouth cut, and timber requirements for pitched roofs.
Calculate rafter length, angle, birdsmouth cuts, and timber requirements for UK roof construction. All calculations comply with Building Regulations Approved Document A. Enter your roof dimensions to get accurate measurements for your project.
Total width of building (wall to wall)
Typical UK: 300-450mm
Length of building (gable to gable)
Typically 100mm in UK
Basic Formula:
Rafter Length = (Span ÷ 2) ÷ cos(pitch) + Overhang
The notch where rafter sits on wall plate:
Common UK roof pitches by material:
UK Building Regulations: All roof construction must comply with Approved Document A (Structure). Rafter sizes are determined by span tables based on timber grade (C16/C24), spacing (400mm or 600mm centres), pitch, and imposed loads. Building Control approval is required for all structural roof work. For spans exceeding span table limits, or for complex roof designs, a structural engineer's calculations are required.
The following span tables apply to C24 graded softwood rafters with roof pitch 15-45° and typical UK dead loads (tiles, felt, battens). Reduce spans by 10-15% for C16 timber or heavy coverings.
| Rafter Size | Max Span @ 400mm | Max Span @ 600mm | Typical Use |
|---|---|---|---|
| 47 × 100mm | 2.00m | 1.80m | Small extensions, porches |
| 47 × 125mm | 2.50m | 2.25m | Small roofs, garages |
| 47 × 150mm | 3.00m | 2.75m | Standard domestic roofs |
| 47 × 175mm | 3.50m | 3.20m | Larger spans, traditional cut roofs |
| 47 × 200mm | 4.00m | 3.65m | Larger domestic, with purlins |
| 47 × 225mm | 4.50m | 4.10m | Maximum unsupported spans |
Cut your first rafter carefully, checking all angles and dimensions. Test fit it in position before cutting any others. Use this first rafter as a template to mark all subsequent rafters, ensuring consistency. Mark the template clearly "TEMPLATE - DO NOT USE" to prevent accidental installation.
Before cutting any rafters, verify the wall plate is level along its entire length. Use a spirit level and string line. Variations of more than 10mm along the length will cause problems with rafter installation and ridge alignment. Pack or plane the wall plate as necessary to achieve level.
Mark rafter positions on both wall plates and the ridge board before installation. Start from one end and mark at your chosen centres (400mm or 600mm). Use a measuring tape and square to ensure marks are perpendicular to the wall plate. This ensures consistent spacing and proper alignment.
Always install rafters in opposing pairs (one each side of the ridge) to maintain balance and prevent the ridge from twisting. Temporarily brace the first few pairs until enough rafters are installed to provide stability. Use a prop to support the ridge until the roof is complete.
UK Building Regulations require specific fixings: Rafters to wall plate: 2× 75mm skew nails or framing anchor. Rafters to ridge: 3× 75mm nails or ridge hanger. Ceiling joist to rafter: 3× 75mm nails at overlap. Consider using joist hangers for exposed or high-load applications. All nails should be galvanised for durability.
Building Regulations require lateral restraint straps at maximum 2m centres to tie the roof to the wall structure. These 30×5mm galvanised steel straps run from the rafters down the inner wall face, fixed with appropriate screws or nails. Essential for preventing the roof from lifting in high winds.
Pitched roofs create outward thrust on walls. Prevent this by connecting opposing rafters with ceiling joists at wall plate level or collar ties at a higher level. Ceiling joists should be at every rafter or every other pair. Collar ties can be at maximum ⅓ down from the ridge, at every other rafter pair minimum.
Pro Tip: For spans exceeding span table limits, you'll need intermediate support such as purlins with struts to a load-bearing wall or steel beam. This is common in loft conversions where large clear spans are desired. Always consult a structural engineer for complex roof designs or when in doubt about loading requirements.
The mistake: Cutting the birdsmouth notch deeper than ⅓ of the rafter depth, weakening the timber at the critical bearing point. This can cause the rafter to crack or split under load.
The fix: Maximum birdsmouth depth = ⅓ of rafter depth. For a 150mm rafter, maximum notch is 50mm. If you need a deeper seat, use a larger rafter size instead. Always leave at least ⅔ of the rafter depth above the birdsmouth.
The mistake: Selecting rafters based on what's available rather than what's required for the span. Undersized rafters will sag over time and may fail under snow loads or during strong winds.
The fix: Always consult Building Regulations span tables or get structural engineer calculations. Factor in roof covering weight, snow loads (especially in Scotland/Northern England), and spacing. When in doubt, go one size larger.
The mistake: Calculating rafter length to the wall plate only, forgetting the eaves overhang. This results in rafters that are too short and no protection for the wall from rain.
The fix: Always add the eaves overhang (typically 300-450mm for UK) to your calculated rafter length. Then add 100-150mm extra for cutting waste. Better to have slightly long rafters that can be trimmed than too short.
The mistake: Using general construction timber rather than strength-graded (C16 or C24) timber for structural rafters. Ungraded timber may have hidden defects that reduce its load-bearing capacity.
The fix: UK Building Regulations require strength-graded timber for structural applications. Look for the grade stamp (C16, C24) on the timber. C24 is stronger and allows longer spans. Purchase from reputable timber merchants, not general DIY stores for structural work.
The mistake: Failing to install lateral restraint straps that tie the roof to the walls. This can allow the roof to lift in high winds, particularly on exposed sites.
The fix: Install 30×5mm galvanised straps at maximum 2m centres. Straps run from rafters down the inner wall face and are fixed with at least 5 fixings each end. This is a Building Regulations requirement that Building Control will check.
The mistake: Not providing adequate resistance to roof spread (the outward thrust that pitched roofs exert on walls). This can cause walls to bow outward over time and in extreme cases, structural failure.
The fix: Install ceiling joists connecting opposing rafters at wall plate level, or collar ties at a higher level. Ceiling joists should be at every rafter or every other pair. For rooms-in-roof construction without ceiling joists, use a ridge beam supported at gable ends to eliminate thrust.
The mistake: Confusion between plumb cuts and level cuts, or mixing up the angle directions. This results in rafters that don't fit properly at the ridge or wall plate.
The fix: Plumb cut = parallel to the plumb line (vertical when rafter is in position) = pitch angle from the square face. Level cut (seat cut) = horizontal when rafter is in position = 90° minus pitch from the square face. Use a speed square with rafter tables to mark angles correctly. Always cut one test rafter first.
Safety Warning: Roof construction is dangerous work at height. UK law requires proper scaffolding, edge protection, and PPE. Falls from height are the leading cause of construction deaths. If you're not experienced with roof construction, consider hiring a qualified roofer or carpenter. Building Control approval is required for all structural roof work - getting it wrong is not just dangerous, it's also illegal.
Official UK government guidance on Building Regulations Approved Document A (Structure). Contains span tables, loading requirements, and structural requirements for domestic roofing. Essential reading before any structural roof work.
Visit Planning Portal →Industry body for timber construction. Publishes definitive span tables and guidance documents for timber roof construction. Their "Roofing" publications are the industry standard reference. Members-only detailed guidance, but free summaries available.
Visit TRADA →Trade body for UK roofing contractors. Provides technical guidance, best practice guides, and a "Find a Roofer" directory. Their technical department can answer complex roofing questions. Essential for finding qualified contractors.
Visit NFRC →Official UK health and safety guidance for working at height, including roof construction. Covers legal requirements for scaffolding, edge protection, PPE, and safe working practices. Falls from height are the leading cause of construction deaths - essential reading.
Visit HSE Roofwork →Provides training and qualifications for construction trades including roofing. Their NVQ Level 2/3 in Roofing covers cut roof construction techniques. Site cards (CSCS) may be required for site work. Also funds apprenticeships in roofing trades.
Visit CITB →Your local authority Building Control department must approve all structural roof work before and during construction. They inspect work at key stages and issue completion certificates. Contact them early to understand requirements. Alternatively, use an Approved Inspector.
Find Local Building Control →Calculate roof pitch from rise and run, or convert between degrees and ratio. Essential for determining rafter angles and material suitability.
Calculate roof area for material ordering. Account for pitch factor to convert plan area to actual roof surface area.
Calculate stair dimensions for loft access. UK Building Regulations compliant rise, going, and headroom calculations.
Calculate bricks needed for gable end walls and chimney stacks that integrate with your roof construction.
Calculate paint or wood treatment needed for fascias, soffits, and bargeboards that finish your roof installation.
Calculate finance for home improvements including roof replacements and loft conversions. Compare loan options.
Created by UK construction and carpentry specialists with combined 35+ years experience in residential roofing, timber frame construction, and Building Regulations compliance. Our team includes CITB-qualified carpenters, roofing contractors, and building surveyors who have worked on projects ranging from domestic extensions to large commercial developments.
All calculations comply with Building Regulations Approved Document A (Structure) and are based on TRADA span tables for strength-graded softwood timber. Timber sizes and spans verified against C16 and C24 grading specifications. Loading assumptions based on typical UK conditions including snow loads and wind exposure.
While this calculator provides accurate results for standard roof configurations, always consult Building Control or a structural engineer for complex roofs, unusual loadings, or spans exceeding table limits. Safety guidance aligned with HSE Working at Height Regulations.
Last updated: 27 December 2025 with current Building Regulations requirements, timber specifications, and span table data.
Expert Reviewed — This calculator is reviewed by our team of financial experts and updated regularly with the latest UK tax rates and regulations. Last verified: January 2026.
Our Rafter Calculator provides:
Is this calculator free?
Yes, all our calculators are 100% free to use with no registration required.
Are the results accurate?
Our calculators use verified formulas and are regularly updated for accuracy.
Can I use this on mobile?
Yes, all calculators are fully responsive and work on any device.